![]() ![]() We do not indicate circuit number connections in two places, this is accomplished in Revit only. We do not indicate circuit numbers on the SKM single line diagram. This is quite similar to the coordination review of the mechanical equipment schedules and electrical equipment schedules to resolve potential conflicting and/or missing information. There isn't an efficient way to avoid this, and it is something that should be reviewed at the 95% review (Drawings 100% complete). Switchboard Schedules and Distribution Panel Schedules and the (SKM) OCP devices connected to Busses. There is duplication of OCP devices that are indicated in (Revit). We import/link the SKM DXF file of the single line diagram into Revit. There is no possible way that Revit can accomplish what SKM does for these functions. Minimize Overlap Between SKM Power Tools and RevitĪt LHB, we also use SKM for the single line diagram, arc flash evaluation, and short circuit calculations. Thus, we have to do things, what little can be done, manually. As I mentioned in yesterday's post, there are no tools to connect SKM Power Tools to Revit that I am aware of. ![]()